Motorenregelung MST 101 für AC-Motoren
- valves,
- pumps,
- thermal units, etc.
MST 101 with RC Protection
General Technical Data MST 101
Operating voltage |
160...253 V AC; 50 Hz |
Fuse internally |
80 mA, time-lag |
Energize |
approx. 5 VA |
Control accuracy, based on the control range end value |
± 1,0 % |
Actual value |
|
Measurement-/Inputsignal AC (converter) Measurement-/Inputsignal DC |
0...253 V max. 0...15 V max. |
Input impedanz - AC Input |
≥ 90 kOhm |
Input impedanz - DC Eingang |
> 5 kOhm |
Set Point Setting (reference signal) per Jumper selection
|
1 bis 100kOhm Uref : 0...10V DC; input impedanz >1MOhm,
ripple: max.2 mV
|
Output |
|
|
|
Output switching capacity (Triac-NO) |
130 VA; modifiable with change-over relay 250V/10A |
Response / delay of the outputs |
10 ms |
|
MOSFET-Level 15V DC High Level |
|
Potential free switchable connection 250VAC/16A (modifiable release) |
Control rate |
Depending on the used motor |
Control parameters
|
47 mV max. (Can be reduced in four steps by means of jumpers) |
Mass |
approx. 330 g |
Protection degree |
IP20 |
Ambient temperature |
+5°C bis + 40°C |
Storage temperature |
+5 °C bis +80 °C |
Dimension Housing (BxHxT) |
(70x90x60) mm |
Install |
DIN-top-rail |
Approbation |
CE, EN61000-6-3, EN61010-1 |